Compute the transformer''s all-day efficiency

Assignment Help Chemical Engineering
Reference no: EM131154354

A single-phase, 10-kVA, 2300:230-V, 60-Hz, two-winding distribution transformer is connected as an autotransformer to step up the voltage from 2300 V to 2530 V.

(a) Draw a schematic diagram of the arrangement showing all the voltages and currents while delivering full load.

(b) Find the permissible kVA rating of the autotransformer if the winding currents are not to exceed those for full-load operation as a two winding transformer. How much of that is transformed by electromagnetic induction?

(c) Based on the data given for the two-winding transformer in Problem 11.4.1, compute the efficiency of the autotransformer corresponding to full load and 0.8 lagging power factor. Comment on why the efficiency of the autotransformer is higher than that of the two-winding transformer.

Problem 11.4.1

These data were obtained from tests carried out on a 10-kVA, 2300:230-V, 60-Hz distribution transformer:

• Open-circuit test, with low-voltage winding excited: applied voltage 230 V, current 0.45 A, input power 70 W

• Short-circuit test, with high-voltage winding excited: applied voltage 120 V, current 4.35 A, input power 224 W

(a) Compute the efficiency of the transformer when it is delivering full load at 230 V and 0.85 power factor lagging.

(b) Find the efficiency of the transformer when it is delivering 7.5 kVA at 230 V and 0.85 power factor lagging.

(c) Determine the fraction of rating at which the transformer efficiency is a maximum, and calculate the efficiency corresponding to that load if the transformer is delivering the load at 230 V and a power factor of 0.85.

(d) The transformer is operating at a constant load power factor of 0.85 on this load cycle: 0.85 full load for 8 hours, 0.60 full load for 12 hours, and no load for 4 hours. Compute the transformer's all-day (or energy) efficiency.

(e) If the transformer is supplying full load at 230 V and 0.8 lagging power factor, determine the voltage regulation of the transformer. Also, find the power factor at the high-voltage terminals.

Reference no: EM131154354

Questions Cloud

Compute the voltage regulation : Draw a schematic diagram of transformer connections, and develop a per-phase equivalent circuit.
How will you support the arts in the future : Write a summary of how you would like to see the arts made more a part of your community. Is there anything you can do to make this happen? How will you support the arts in the future?
Find the efficiency of the transformer for 70% full load : A three-phase, 600-kVA, 2300:230-V, Y-Y transformer bank has an iron loss of 4400 W and a full load copper loss of 7600 W. Find the efficiency of the transformer for 70% full load at 230 V and 0.85 power factor.
Describe the norm you violated : In your paper, you will need to address the following: Describe the norm you violated. Explain how you felt. Discuss the reactions people had to you
Compute the transformer''s all-day efficiency : Draw a schematic diagram of the arrangement showing all the voltages and currents while delivering full load.
How do the near-architectural elements fit with lush paint : What does the diagonal of the bed provide? Now move close and examine the paint work. How do the near-architectural elements fit with the lush paint?
Describe the organization strategy toward change : Describe the organization's strategy toward change. What is the current mission, vision, and culture? Based on the changes that you are recommending this organization undertake, do you believe that they need to change their mission, vision, or cul..
Draw the schematic diagram of the arrangement : Draw the schematic diagram of the arrangement, label all the currents and voltages, and calculate all the quantities involved.
Disadvantages of low power factor : What are the disadvantages of low power factor? How can it be improved?

Reviews

Write a Review

Chemical Engineering Questions & Answers

  Why a substance heated at a fast rate

Why a substance is being heated at a fast rate the temperature of decomposition

  Design variables necessary for sizing equipment

Assist with the setting of design variables necessary for sizing equipment

  Solve the initial value problem

Use Laplace transformation to solve the initial value problem

  Baffled tank with a six blade turbine agitator

Equal rates of mass transfer for the production of the fine chemical are required. This is often required for certain types of organic synthesis.

  Adsorption and membranes processes

Application of reverse osmosis principles for the desalination of sea water

  Evaluation of a new chemical manufacturing process

Prepare the design and evaluation of a new chemical manufacturing process.

  Adsorption and membrane processes

Adsorption and Membrane Processes

  Draw t-s diagram of the cycle

Draw T-S diagram of the cycle.

  Materials chemistry find potential energy between two atoms

The potential energy between two atoms A and B are constants and r the interatomic separation distance.

  Implications of the future of fabrication for international

Implications of the future of fabrication for international trade, transportation, and logistics

  Evaluate the work done by the gas

The atmospheric pressure of 100k Pa acts on the other side of the piston. The gas is heated until the volume is doubled and the final pressure is 500 kPa. Calculate the work done by the gas.

  Evaluate particle diameter at different gas velocities

Evaluate particle diameter at different terminal gas velocities

Free Assignment Quote

Assured A++ Grade

Get guaranteed satisfaction & time on delivery in every assignment order you paid with us! We ensure premium quality solution document along with free turntin report!

All rights reserved! Copyrights ©2019-2020 ExpertsMind IT Educational Pvt Ltd