A Y-connected capacitor bank is connected in parallel with the loads of Problem 2.13. Find
a) The total kvar and capacitance per phase in uF to improve the overall power factor to 0.8 lagging.
b) The corresponding line current.
Problem 2.13
Three loads are connected in parallel across a 12.47 kV three-phase supply. The first is a resistive 60 kW load, the second is a motor (inductive) load of 60 kW and 660 kvar, and the third is a capacitive load drawing 240 kW at 0.8 p.f. Find the total apparent power, power factor, and supply current.
A 100 MW power station delivers 100 MW for 2 hours, 50 MW for 6 hours and is shut down for the rest of each day. It is also shut down for maintenance for 45 days each year. Calculate its annual load factor.
in a hydroelectric generating station the difference in level between ,the water surface and turbine driving the generators is 425 meters.if 1250 liters of water is required to generate 1 kwh of electric energy.find the overall efficiency
1. Derive boundary conditions for electric fields (both for tangential and normal components) 2. Derive boundary conditions for magnetic fields (both for tangential and normal components) 3. Why boundary conditions are so important in electromagnetic..
The state machine has two inputsignals, LEFT and RIGHT, that carry the driver's request fora left turn or a right turn. It also has anemergency flasher input, HAZ, that requires the tail lights to beoperating in hazard mode - all six lights flashi..
Desired D.C. Output : 10 V Load Variation: 0.3 kilo-ohms - 10 kilo-ohms Ripple Factor: Less than 0.1% for 2 kilo-ohms load Load Regulation: Better than 3 mV for a 1 mA change in load current
Use an iterative solution of the diode logarithmic voltage-current relationship.
A 5-MVA, 66:13.2kV, three-phase transformer supplies a three-phase resistive load of 4,500kW at 13.2kV. What is the load resistance in ohms as measured from the line-to-neutral on the high-voltage side of the transformer, if it is connected in Y-Y..
a number of students are answering a questionnaire form that has 55 questions. answer to each question is given as an
The strength of longitudinal joint in Fig. 1-17 is 33 kips/ft, whereas for the girth is 16 kips/ft. Calculate the maximum diameter of the cylinder tank if the internal pressure is 150 psi.
An amplifier operating from a single 15-V supply provides a 12-V peak-to-peak sine-wave signal to a I-ill load and draws negligible input current from the signal source. The de current drawn from the 15-v supply is 8mA.
(a) Draw the equivalent circuit. (b) Determine the ohmic value of the impedances. (c) Calculate the source current in amperes and in percent if the generator operating voltage is 3.8 kV (line-to-line) and a reactance of X=125% is connected in seri..
An amplifier represented with an input resistance of 10k ohm, an output resistance of 1k ohm, and the open circuit voltage gain of 1000 V/V is connected to a signal source of 10 mV peak amplitude with an internal resistance of 100k ohm.
Get guaranteed satisfaction & time on delivery in every assignment order you paid with us! We ensure premium quality solution document along with free turntin report!
whatsapp: +1-415-670-9521
Phone: +1-415-670-9521
Email: [email protected]
All rights reserved! Copyrights ©2019-2020 ExpertsMind IT Educational Pvt Ltd